IEEE C37.09-2018/Cor 1:2021
IEEE Standard Test Procedure for AC High-Voltage Circuit Breakers with Rated Maximum Voltage Above 1000 V - Corrigendum 1
Summary
Corrigendum Standard - Active.
This corrigendum is to improve the current IEEE Std C37.09(TM).
a. Clause 4.10.4 the ratio of zero and positive sequence currents in single phase capacitive switching procedure should be less than 3.0 rather than greater than 3.0.
b. Errors in clause 4.10.9.1.8 and 4.10.9.2.7 regarding reference to the procedure for separate making tests.
c. 4.10.9.1.3 change in punctuation for clarity
d. Throughout document unify terms for rated voltage, including in equations to use "Ur" rather than "V"
f. Clause 4.1.2 i) is missing some words required for clear meaning.
g. Correct references and terms used by both C37.04 and C37.09 so they are identical
h. Remove classification of tests in the Scope as only design tests are covered.
i. Clauses 4.5.7 and 4.5.8.1 to make clear that average of the test impulses shall be equal or higher than rated value
j. clarify in 4.8.2.7. which tests to be performed at minimum control voltage
k. Correct item list in 4.8.2.3.3
l. Correct title of Figure 3 and correct Figure 4 (example for incorrect grounding condition given)
m. Correct arcing window/multiplier in Table 5
n. Correct item list in 4.8.5.4.3
o. correct the steps of electrical degrees for capacitance switching duties in 4.10.9.2.7 (30° for single- and 10° for three phase)
p. further minor items depending upon agreement in the WG
This corrigendum is to improve the current IEEE Std C37.09(TM).
a. Clause 4.10.4 the ratio of zero and positive sequence currents in single phase capacitive switching procedure should be less than 3.0 rather than greater than 3.0.
b. Errors in clause 4.10.9.1.8 and 4.10.9.2.7 regarding reference to the procedure for separate making tests.
c. 4.10.9.1.3 change in punctuation for clarity
d. Throughout document unify terms for rated voltage, including in equations to use "Ur" rather than "V"
f. Clause 4.1.2 i) is missing some words required for clear meaning.
g. Correct references and terms used by both C37.04 and C37.09 so they are identical
h. Remove classification of tests in the Scope as only design tests are covered.
i. Clauses 4.5.7 and 4.5.8.1 to make clear that average of the test impulses shall be equal or higher than rated value
j. clarify in 4.8.2.7. which tests to be performed at minimum control voltage
k. Correct item list in 4.8.2.3.3
l. Correct title of Figure 3 and correct Figure 4 (example for incorrect grounding condition given)
m. Correct arcing window/multiplier in Table 5
n. Correct item list in 4.8.5.4.3
o. correct the steps of electrical degrees for capacitance switching duties in 4.10.9.2.7 (30° for single- and 10° for three phase)
p. further minor items depending upon agreement in the WG
Notes
Active
Technical characteristics
| Publisher | Institute of Electrical and Electronics Engineers (IEEE) |
| Publication Date | 06/03/2021 |
| Edition | |
| Page Count | 21 |
| EAN | --- |
| ISBN | --- |
| Weight (in grams) | --- |
| Brochures |
|
Amendments modifies
11/04/2019
Active
, Modified
Most Recent
Previous versions
11/04/2019
Active
, Modified
Most Recent
02/05/2007
Superseded
, Confirmed
Historical
16/09/2005
Superseded
, Confirmed
Historical
28/03/2000
Superseded
, Confirmed
Historical
12/06/1992
Superseded
Historical
11/08/1991
Superseded
Historical
18/11/1985
Superseded
, Confirmed
Historical
30/06/1984
Superseded
Historical
28/11/1980
Superseded
, Confirmed
Historical