Components
4
Twig Components
16
Render Count
16
ms
Render Time
238.0
MiB
Memory Usage
Components
| Name | Metadata | Render Count | Render Time |
|---|---|---|---|
| ProductState |
"App\Twig\Components\ProductState"components/ProductState.html.twig |
7 | 1.74ms |
| ProductMostRecent |
"App\Twig\Components\ProductMostRecent"components/ProductMostRecent.html.twig |
7 | 5.40ms |
| ProductType |
"App\Twig\Components\ProductType"components/ProductType.html.twig |
1 | 0.22ms |
| ProductCard |
"App\Twig\Components\ProductCard"components/ProductCard.html.twig |
1 | 10.45ms |
Render calls
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.36 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#93114 +product: App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } +appearance: "state-withdrawn" +labels: [ "Withdrawn" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductType | App\Twig\Components\ProductType | 238.0 MiB | 0.22 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductType {#93294 +product: App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } +label: "Standard" -typeAttributeCode: "type" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 0.73 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#93369 +product: App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } +label: "Most Recent" +icon: "check-xs" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.32 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#100435 +product: App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } +appearance: "state-suspended" +labels: [ "Superseded" "Confirmed" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 1.01 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#100506 +product: App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } +label: "Historical" +icon: "historical" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.20 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#107161 +product: App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } +appearance: "state-withdrawn" +labels: [ "Withdrawn" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 0.67 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#107203 +product: App\Entity\Product\Product {#7311 #id: 10383 #code: "IEEE00004283" #attributes: Doctrine\ORM\PersistentCollection {#7701 …} #variants: Doctrine\ORM\PersistentCollection {#7744 …} #options: Doctrine\ORM\PersistentCollection {#7916 …} #associations: Doctrine\ORM\PersistentCollection {#7900 …} #createdAt: DateTime @1751039028 {#7274 : 2025-06-27 17:43:48.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607004 {#7322 : 2025-08-08 00:50:04.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#7922 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#7921 #locale: "en_US" #translatable: App\Entity\Product\Product {#7311} #id: 36541 #name: "IEEE 367:2012" #slug: "ieee-367-2012-ieee00004283-242035" #description: """ Revision Standard - Inactive-Reserved.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This standard provides guidance for the calculation of power station GPR and LI voltages and guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. b) The zone of influence (ZOI) of the power station GPR. c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors. d) The channel time requirements for metallic telecommunication facilities where non-interruptible channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Inactive-Reserved" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#7534 …} #channels: Doctrine\ORM\PersistentCollection {#7628 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#7613 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#7645 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#7321 …} -apiLastModifiedAt: DateTime @1754517600 {#7317 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1684706400 {#7292 : 2023-05-22 00:00:00.0 Europe/Paris (+02:00) } -author: "" -publishedAt: DateTime @1337551200 {#7318 : 2012-05-21 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: DateTime @1680127200 {#7316 : 2023-03-30 00:00:00.0 Europe/Paris (+02:00) } -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 168 -documents: Doctrine\ORM\PersistentCollection {#7465 …} -favorites: Doctrine\ORM\PersistentCollection {#7500 …} } +label: "Most Recent" +icon: "check-xs" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.19 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#107268 +product: App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } +appearance: "state-suspended" +labels: [ "Superseded" "Confirmed" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 0.60 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#107295 +product: App\Entity\Product\Product {#100381 #id: 8495 #code: "IEEE00000566" #attributes: Doctrine\ORM\PersistentCollection {#100362 …} #variants: Doctrine\ORM\PersistentCollection {#100359 …} #options: Doctrine\ORM\PersistentCollection {#100355 …} #associations: Doctrine\ORM\PersistentCollection {#100357 …} #createdAt: DateTime @1751037466 {#100388 : 2025-06-27 17:17:46.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#100361 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#100372 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#100399 #locale: "en_US" #translatable: App\Entity\Product\Product {#100381} #id: 28989 #name: "IEEE 367:1996 (R2002)" #slug: "ieee-367-1996-r2002-ieee00000566-240147" #description: """ Revision Standard - Superseded.<br />\n Guidance for the calculation of power station ground potential rise (GPR) and longitudinal induction (LI) voltages is provided, as well as guidance for their appropriate reduction from worst-case values, for use in metallic telecommunication protection design.<br />\n \t\t\t\t<br />\n This recommended practice provides guidance for the calculation of power station GPR and LI voltages, as well as guidance for their appropriate reduction from worst-case values for use in metallic telecommunication protection design. Information is also included for the determination of the following: a) The fault current and the earth return current. (The probability, waveform, and duration of these currents and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X / R ratio are discussed.)<br />\n b) The zone of inßuence (ZOI) of the power station GPR.<br />\n c) The calculation of the inducing currents, the mutual impedance between power and metallic telecommunication facilities, and shield factors.<br />\n d) The channel time requirements for metallic telecommunication facilities where non-interruptible<br />\n channels are required for protective relaying.<br />\n To review and update existing standard 367-1987 as required. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#100370 …} #channels: Doctrine\ORM\PersistentCollection {#100364 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#100368 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#100366 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#100379 …} -apiLastModifiedAt: DateTime @1754517600 {#100348 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#100387 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @849308400 {#100386 : 1996-11-30 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: DateTime @1016665200 {#100380 : 2002-03-21 00:00:00.0 Europe/Paris (+01:00) } -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 144 -documents: Doctrine\ORM\PersistentCollection {#100377 …} -favorites: Doctrine\ORM\PersistentCollection {#100375 …} } +label: "Historical" +icon: "historical" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.18 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#107083 #id: 8494 #code: "IEEE00000565" #attributes: Doctrine\ORM\PersistentCollection {#107099 …} #variants: Doctrine\ORM\PersistentCollection {#107101 …} #options: Doctrine\ORM\PersistentCollection {#107105 …} #associations: Doctrine\ORM\PersistentCollection {#107103 …} #createdAt: DateTime @1751037465 {#107075 : 2025-06-27 17:17:45.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#107072 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107089 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107361 #locale: "en_US" #translatable: App\Entity\Product\Product {#107083} #id: 28985 #name: "IEEE 367:1987" #slug: "ieee-367-1987-ieee00000565-240146" #description: """ Revision Standard - Superseded.<br />\n Guidance is provided for the calculation of interfering voltages and their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of the fault current and earth-return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these ground potential rise (GPR) and longitudinally induced voltage calculations. The zone of influence of the power station GPR; the calculation of the inducing currents; the mutual impedance between power and wire-line telecommunication facilities and shield factors; and the channel time requirements for wire-line telecommunication facilities where noninterruptible channels are required for protective relaying and other purposes are covered.<br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication, protection, and relay engineers in determining the “appropriate” values of power station ground potential rise (GPR) or the longitudinally induced voltages (LI) into wire-line telecommunications facilities (or both) including their probability, waveform, and duration, which are to be used in developing the specifications for systems and component protection. Suitably rated protection devices are required for personnel safety and for the protection and continuity of service for wire-line facilities that either enter electric power stations or that are otherwise exposed to the influence of high-electric power circuits. (See ANSI/IEEE Std 487-1980 [51]) This standard provides guidance for the calculation of these interfering voltages and guidance for their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of (1) The fault current and earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. (2) The zone of influence of the power station GPR. (3) The calculation of the inducing currents, the mutual impedance between (4) The channel time requirements for wire-line telecommunication facilities power and wire-line telecommunication facilities, and shield factors. where noninterruptible channels are required for protective relaying, etc. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107091 …} #channels: Doctrine\ORM\PersistentCollection {#107097 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107093 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107095 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107082 …} -apiLastModifiedAt: DateTime @1754517600 {#107074 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107076 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @578268000 {#107077 : 1988-04-29 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 165 -documents: Doctrine\ORM\PersistentCollection {#107085 …} -favorites: Doctrine\ORM\PersistentCollection {#107087 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#107376 +product: App\Entity\Product\Product {#107083 #id: 8494 #code: "IEEE00000565" #attributes: Doctrine\ORM\PersistentCollection {#107099 …} #variants: Doctrine\ORM\PersistentCollection {#107101 …} #options: Doctrine\ORM\PersistentCollection {#107105 …} #associations: Doctrine\ORM\PersistentCollection {#107103 …} #createdAt: DateTime @1751037465 {#107075 : 2025-06-27 17:17:45.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#107072 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107089 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107361 #locale: "en_US" #translatable: App\Entity\Product\Product {#107083} #id: 28985 #name: "IEEE 367:1987" #slug: "ieee-367-1987-ieee00000565-240146" #description: """ Revision Standard - Superseded.<br />\n Guidance is provided for the calculation of interfering voltages and their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of the fault current and earth-return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these ground potential rise (GPR) and longitudinally induced voltage calculations. The zone of influence of the power station GPR; the calculation of the inducing currents; the mutual impedance between power and wire-line telecommunication facilities and shield factors; and the channel time requirements for wire-line telecommunication facilities where noninterruptible channels are required for protective relaying and other purposes are covered.<br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication, protection, and relay engineers in determining the “appropriate” values of power station ground potential rise (GPR) or the longitudinally induced voltages (LI) into wire-line telecommunications facilities (or both) including their probability, waveform, and duration, which are to be used in developing the specifications for systems and component protection. Suitably rated protection devices are required for personnel safety and for the protection and continuity of service for wire-line facilities that either enter electric power stations or that are otherwise exposed to the influence of high-electric power circuits. (See ANSI/IEEE Std 487-1980 [51]) This standard provides guidance for the calculation of these interfering voltages and guidance for their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of (1) The fault current and earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. (2) The zone of influence of the power station GPR. (3) The calculation of the inducing currents, the mutual impedance between (4) The channel time requirements for wire-line telecommunication facilities power and wire-line telecommunication facilities, and shield factors. where noninterruptible channels are required for protective relaying, etc. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107091 …} #channels: Doctrine\ORM\PersistentCollection {#107097 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107093 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107095 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107082 …} -apiLastModifiedAt: DateTime @1754517600 {#107074 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107076 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @578268000 {#107077 : 1988-04-29 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 165 -documents: Doctrine\ORM\PersistentCollection {#107085 …} -favorites: Doctrine\ORM\PersistentCollection {#107087 …} } +appearance: "state-suspended" +labels: [ "Superseded" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 0.61 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#107083 #id: 8494 #code: "IEEE00000565" #attributes: Doctrine\ORM\PersistentCollection {#107099 …} #variants: Doctrine\ORM\PersistentCollection {#107101 …} #options: Doctrine\ORM\PersistentCollection {#107105 …} #associations: Doctrine\ORM\PersistentCollection {#107103 …} #createdAt: DateTime @1751037465 {#107075 : 2025-06-27 17:17:45.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#107072 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107089 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107361 #locale: "en_US" #translatable: App\Entity\Product\Product {#107083} #id: 28985 #name: "IEEE 367:1987" #slug: "ieee-367-1987-ieee00000565-240146" #description: """ Revision Standard - Superseded.<br />\n Guidance is provided for the calculation of interfering voltages and their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of the fault current and earth-return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these ground potential rise (GPR) and longitudinally induced voltage calculations. The zone of influence of the power station GPR; the calculation of the inducing currents; the mutual impedance between power and wire-line telecommunication facilities and shield factors; and the channel time requirements for wire-line telecommunication facilities where noninterruptible channels are required for protective relaying and other purposes are covered.<br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication, protection, and relay engineers in determining the “appropriate” values of power station ground potential rise (GPR) or the longitudinally induced voltages (LI) into wire-line telecommunications facilities (or both) including their probability, waveform, and duration, which are to be used in developing the specifications for systems and component protection. Suitably rated protection devices are required for personnel safety and for the protection and continuity of service for wire-line facilities that either enter electric power stations or that are otherwise exposed to the influence of high-electric power circuits. (See ANSI/IEEE Std 487-1980 [51]) This standard provides guidance for the calculation of these interfering voltages and guidance for their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of (1) The fault current and earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. (2) The zone of influence of the power station GPR. (3) The calculation of the inducing currents, the mutual impedance between (4) The channel time requirements for wire-line telecommunication facilities power and wire-line telecommunication facilities, and shield factors. where noninterruptible channels are required for protective relaying, etc. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107091 …} #channels: Doctrine\ORM\PersistentCollection {#107097 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107093 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107095 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107082 …} -apiLastModifiedAt: DateTime @1754517600 {#107074 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107076 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @578268000 {#107077 : 1988-04-29 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 165 -documents: Doctrine\ORM\PersistentCollection {#107085 …} -favorites: Doctrine\ORM\PersistentCollection {#107087 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#107428 +product: App\Entity\Product\Product {#107083 #id: 8494 #code: "IEEE00000565" #attributes: Doctrine\ORM\PersistentCollection {#107099 …} #variants: Doctrine\ORM\PersistentCollection {#107101 …} #options: Doctrine\ORM\PersistentCollection {#107105 …} #associations: Doctrine\ORM\PersistentCollection {#107103 …} #createdAt: DateTime @1751037465 {#107075 : 2025-06-27 17:17:45.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#107072 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107089 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107361 #locale: "en_US" #translatable: App\Entity\Product\Product {#107083} #id: 28985 #name: "IEEE 367:1987" #slug: "ieee-367-1987-ieee00000565-240146" #description: """ Revision Standard - Superseded.<br />\n Guidance is provided for the calculation of interfering voltages and their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of the fault current and earth-return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these ground potential rise (GPR) and longitudinally induced voltage calculations. The zone of influence of the power station GPR; the calculation of the inducing currents; the mutual impedance between power and wire-line telecommunication facilities and shield factors; and the channel time requirements for wire-line telecommunication facilities where noninterruptible channels are required for protective relaying and other purposes are covered.<br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication, protection, and relay engineers in determining the “appropriate” values of power station ground potential rise (GPR) or the longitudinally induced voltages (LI) into wire-line telecommunications facilities (or both) including their probability, waveform, and duration, which are to be used in developing the specifications for systems and component protection. Suitably rated protection devices are required for personnel safety and for the protection and continuity of service for wire-line facilities that either enter electric power stations or that are otherwise exposed to the influence of high-electric power circuits. (See ANSI/IEEE Std 487-1980 [51]) This standard provides guidance for the calculation of these interfering voltages and guidance for their appropriate reduction from worst-case values for use in wire-line telecommunication protection design. Information is also included for the determination of (1) The fault current and earth return current levels; their probability, waveform, and duration; and the impedance to remote earthing points used in these GPR and LI calculations as well as the effective X/R ratio. (2) The zone of influence of the power station GPR. (3) The calculation of the inducing currents, the mutual impedance between (4) The channel time requirements for wire-line telecommunication facilities power and wire-line telecommunication facilities, and shield factors. where noninterruptible channels are required for protective relaying, etc. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107091 …} #channels: Doctrine\ORM\PersistentCollection {#107097 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107093 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107095 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107082 …} -apiLastModifiedAt: DateTime @1754517600 {#107074 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107076 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @578268000 {#107077 : 1988-04-29 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 165 -documents: Doctrine\ORM\PersistentCollection {#107085 …} -favorites: Doctrine\ORM\PersistentCollection {#107087 …} } +label: "Historical" +icon: "historical" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.22 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#107112 #id: 11662 #code: "IEEE00006422" #attributes: Doctrine\ORM\PersistentCollection {#107129 …} #variants: Doctrine\ORM\PersistentCollection {#107131 …} #options: Doctrine\ORM\PersistentCollection {#107135 …} #associations: Doctrine\ORM\PersistentCollection {#107133 …} #createdAt: DateTime @1751039877 {#107107 : 2025-06-27 17:57:57.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607611 {#107108 : 2025-08-08 01:00:11.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107119 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107494 #locale: "en_US" #translatable: App\Entity\Product\Product {#107112} #id: 41657 #name: "ANSI/IEEE 367:1979" #slug: "ansi-ieee-367-1979-ieee00006422-243314" #description: """ - Superseded.<br />\n <br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication and protective relay engineers in determining the maximum power station ground potential rise, or induced voltages, or both. Suitably rated protective devices are required for personnel safety and for the protection and continuity of service of wire line telecommunication facilities entering electrical power stations, or otherwise exposed to the influence of electrical power circuits. This guide provides guidance for the calculation of these maximum voltages and for the acceptance of values lower than maximum, as well as the time requirements of communication channels where protective relaying is involved """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107121 …} #channels: Doctrine\ORM\PersistentCollection {#107127 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107123 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107125 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107113 …} -apiLastModifiedAt: DateTime @1754517600 {#107109 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107110 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @314319600 {#107111 : 1979-12-18 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 56 -documents: Doctrine\ORM\PersistentCollection {#107115 …} -favorites: Doctrine\ORM\PersistentCollection {#107117 …} } "showFullLabel" => "true" ] |
|||
| Attributes | [ "showFullLabel" => "true" ] |
|||
| Component | App\Twig\Components\ProductState {#107509 +product: App\Entity\Product\Product {#107112 #id: 11662 #code: "IEEE00006422" #attributes: Doctrine\ORM\PersistentCollection {#107129 …} #variants: Doctrine\ORM\PersistentCollection {#107131 …} #options: Doctrine\ORM\PersistentCollection {#107135 …} #associations: Doctrine\ORM\PersistentCollection {#107133 …} #createdAt: DateTime @1751039877 {#107107 : 2025-06-27 17:57:57.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607611 {#107108 : 2025-08-08 01:00:11.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107119 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107494 #locale: "en_US" #translatable: App\Entity\Product\Product {#107112} #id: 41657 #name: "ANSI/IEEE 367:1979" #slug: "ansi-ieee-367-1979-ieee00006422-243314" #description: """ - Superseded.<br />\n <br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication and protective relay engineers in determining the maximum power station ground potential rise, or induced voltages, or both. Suitably rated protective devices are required for personnel safety and for the protection and continuity of service of wire line telecommunication facilities entering electrical power stations, or otherwise exposed to the influence of electrical power circuits. This guide provides guidance for the calculation of these maximum voltages and for the acceptance of values lower than maximum, as well as the time requirements of communication channels where protective relaying is involved """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107121 …} #channels: Doctrine\ORM\PersistentCollection {#107127 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107123 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107125 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107113 …} -apiLastModifiedAt: DateTime @1754517600 {#107109 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107110 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @314319600 {#107111 : 1979-12-18 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 56 -documents: Doctrine\ORM\PersistentCollection {#107115 …} -favorites: Doctrine\ORM\PersistentCollection {#107117 …} } +appearance: "state-suspended" +labels: [ "Superseded" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 0.69 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#107112 #id: 11662 #code: "IEEE00006422" #attributes: Doctrine\ORM\PersistentCollection {#107129 …} #variants: Doctrine\ORM\PersistentCollection {#107131 …} #options: Doctrine\ORM\PersistentCollection {#107135 …} #associations: Doctrine\ORM\PersistentCollection {#107133 …} #createdAt: DateTime @1751039877 {#107107 : 2025-06-27 17:57:57.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607611 {#107108 : 2025-08-08 01:00:11.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107119 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107494 #locale: "en_US" #translatable: App\Entity\Product\Product {#107112} #id: 41657 #name: "ANSI/IEEE 367:1979" #slug: "ansi-ieee-367-1979-ieee00006422-243314" #description: """ - Superseded.<br />\n <br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication and protective relay engineers in determining the maximum power station ground potential rise, or induced voltages, or both. Suitably rated protective devices are required for personnel safety and for the protection and continuity of service of wire line telecommunication facilities entering electrical power stations, or otherwise exposed to the influence of electrical power circuits. This guide provides guidance for the calculation of these maximum voltages and for the acceptance of values lower than maximum, as well as the time requirements of communication channels where protective relaying is involved """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107121 …} #channels: Doctrine\ORM\PersistentCollection {#107127 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107123 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107125 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107113 …} -apiLastModifiedAt: DateTime @1754517600 {#107109 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107110 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @314319600 {#107111 : 1979-12-18 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 56 -documents: Doctrine\ORM\PersistentCollection {#107115 …} -favorites: Doctrine\ORM\PersistentCollection {#107117 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#107561 +product: App\Entity\Product\Product {#107112 #id: 11662 #code: "IEEE00006422" #attributes: Doctrine\ORM\PersistentCollection {#107129 …} #variants: Doctrine\ORM\PersistentCollection {#107131 …} #options: Doctrine\ORM\PersistentCollection {#107135 …} #associations: Doctrine\ORM\PersistentCollection {#107133 …} #createdAt: DateTime @1751039877 {#107107 : 2025-06-27 17:57:57.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754607611 {#107108 : 2025-08-08 01:00:11.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#107119 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#107494 #locale: "en_US" #translatable: App\Entity\Product\Product {#107112} #id: 41657 #name: "ANSI/IEEE 367:1979" #slug: "ansi-ieee-367-1979-ieee00006422-243314" #description: """ - Superseded.<br />\n <br />\n \t\t\t\t<br />\n Difficulties are experienced by telecommunication and protective relay engineers in determining the maximum power station ground potential rise, or induced voltages, or both. Suitably rated protective devices are required for personnel safety and for the protection and continuity of service of wire line telecommunication facilities entering electrical power stations, or otherwise exposed to the influence of electrical power circuits. This guide provides guidance for the calculation of these maximum voltages and for the acceptance of values lower than maximum, as well as the time requirements of communication channels where protective relaying is involved """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Determining the Electric Power Station Ground Potential Rise and Induced Voltage from a Power Fault" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#107121 …} #channels: Doctrine\ORM\PersistentCollection {#107127 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#107123 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#107125 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#107113 …} -apiLastModifiedAt: DateTime @1754517600 {#107109 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1578006000 {#107110 : 2020-01-03 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @314319600 {#107111 : 1979-12-18 00:00:00.0 Europe/Paris (+01:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "367" -bookCollection: "" -pageCount: 56 -documents: Doctrine\ORM\PersistentCollection {#107115 …} -favorites: Doctrine\ORM\PersistentCollection {#107117 …} } +label: "Historical" +icon: "historical" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductCard | App\Twig\Components\ProductCard | 238.0 MiB | 10.45 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } "layout" => "vertical" "showPrice" => true "showStatusBadges" => true "additionalClasses" => "product__teaser--with-grey-border" "hasStretchedLink" => true "hoverType" => "shadow" "linkLabel" => "See more" ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductCard {#129147 +product: App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } +layout: "vertical" +showPrice: true +showStatusBadges: true +additionalClasses: "product__teaser--with-grey-border" +linkLabel: "See more" +imageFilter: "product_thumbnail_teaser" +hasStretchedLink: true +backgroundColor: "white" +hoverType: "shadow" } |
|||
| ProductState | App\Twig\Components\ProductState | 238.0 MiB | 0.28 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } ] |
|||
| Attributes | [ "showFullLabel" => false ] |
|||
| Component | App\Twig\Components\ProductState {#129183 +product: App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } +appearance: "state-suspended" +labels: [ "Superseded" ] -stateAttributeCode: "state" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||
| ProductMostRecent | App\Twig\Components\ProductMostRecent | 238.0 MiB | 1.10 ms | |
|---|---|---|---|---|
| Input props | [ "product" => App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } ] |
|||
| Attributes | [] |
|||
| Component | App\Twig\Components\ProductMostRecent {#129261 +product: App\Entity\Product\Product {#129074 #id: 8295 #code: "IEEE00000225" #attributes: Doctrine\ORM\PersistentCollection {#129079 …} #variants: Doctrine\ORM\PersistentCollection {#129077 …} #options: Doctrine\ORM\PersistentCollection {#129072 …} #associations: Doctrine\ORM\PersistentCollection {#129075 …} #createdAt: DateTime @1751037296 {#129068 : 2025-06-27 17:14:56.0 Europe/Paris (+02:00) } #updatedAt: DateTime @1754606304 {#129103 : 2025-08-08 00:38:24.0 Europe/Paris (+02:00) } #enabled: true #translations: Doctrine\ORM\PersistentCollection {#129090 …} #translationsCache: [ "en_US" => App\Entity\Product\ProductTranslation {#129179 #locale: "en_US" #translatable: App\Entity\Product\Product {#129074} #id: 28189 #name: "IEEE 80:2000" #slug: "ieee-80-2000-ieee00000225-239947" #description: """ Revision Standard - Superseded.<br />\n Outdoor ac substations, either conventional or gas-insulated, are covered in this guide. Distribution, transmission, and generating plant substations are also included. With proper caution,the methods described herein are also applicable to indoor portions of such substations, or to sub-stations that are wholly indoors. No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n \t\t\t\t<br />\n This guide is primarily concerned with outdoor ac substations, either conventional or gas-insulated. Distribution, transmission, and generating plant substations are included. With proper caution, the methods described herein are also applicable to indoor portions of such substations, or to substations that are wholly indoors.1 No attempt is made to cover the grounding problems peculiar to dc substations. A quantitative analysis of the effects of lightning surges is also beyond the scope of this guide.<br />\n The intent of this guide is to provide guidance and information pertinent to safe grounding practices in ac substation design. The specific purposes of this guide are to<br />\n a) Establish, as a basis for design, the safe limits of potential differences that can exist in a substation under fault conditions between points that can be contacted by the human body.<br />\n b) Review substation grounding practices with special reference to safety, and develop criteria for a safe design.<br />\n c) Provide a procedure for the design of practical grounding systems, based on these criteria.<br />\n d) Develop analytical methods as an aid in the understanding and solution of typical gradient problems. The concept and use of safety criteria are described in Clause 1 through Clause 8, practical aspects of designing a grounding system are covered in Clause 9 through Clause 13, and procedures and evaluation techniques for the grounding system assessment (in terms of safety criteria) are described in Clause 14 through Clause 20. Supporting material is organized in Annex A through Annex G.<br />\n This guide is primarily concerned with safe grounding practices for power frequencies in the range of 50-60 Hz. The problems peculiar to dc substations and the effects of lightning surges are beyond the scope of this guide. A grounding system designed as described herein will, nonetheless, provide some degree of protection against steep wave front surges entering the substation and passing to earth through its ground electrodes.2<br />\n Othere references should be consulted for more information about these subjects. """ #metaKeywords: null #metaDescription: null #shortDescription: "IEEE Guide for Safety in AC Substation Grounding" -notes: "Superseded" } ] #currentLocale: "en_US" #currentTranslation: null #fallbackLocale: "en_US" #variantSelectionMethod: "match" #productTaxons: Doctrine\ORM\PersistentCollection {#129088 …} #channels: Doctrine\ORM\PersistentCollection {#129081 …} #mainTaxon: Proxies\__CG__\App\Entity\Taxonomy\Taxon {#7309 …} #reviews: Doctrine\ORM\PersistentCollection {#129085 …} #averageRating: 0.0 #images: Doctrine\ORM\PersistentCollection {#129083 …} -supplier: Proxies\__CG__\App\Entity\Supplier\Supplier {#7324 …} -subscriptionCollections: Doctrine\ORM\PersistentCollection {#129095 …} -apiLastModifiedAt: DateTime @1754517600 {#129054 : 2025-08-07 00:00:00.0 Europe/Paris (+02:00) } -lastUpdatedAt: DateTime @1704927600 {#129102 : 2024-01-11 00:00:00.0 Europe/Paris (+01:00) } -author: "" -publishedAt: DateTime @965340000 {#129061 : 2000-08-04 00:00:00.0 Europe/Paris (+02:00) } -releasedAt: null -confirmedAt: null -canceledAt: null -edition: null -coreDocument: "80" -bookCollection: "" -pageCount: 192 -documents: Doctrine\ORM\PersistentCollection {#129094 …} -favorites: Doctrine\ORM\PersistentCollection {#129092 …} } +label: "Historical" +icon: "historical" -mostRecentAttributeCode: "most_recent" -localeContext: Sylius\Component\Locale\Context\CompositeLocaleContext {#1833 …} } |
|||